Beggan, Ciaran; Richardson, Gemma; Thomson, Alan. 2018 Validation of GIC in the GB High Voltage Network. [Lecture] In: EGU General Assembly 2018, Vienna, Austria, 8-13 April 2018. British Geological Survey. (Unpublished)
Abstract
The high-voltage (HV) power network of the mainland Great Britain (GB) consists of over 400 nodes and 750
connections. Using the National Grid Ten-Year Electricity Statement, we have developed an up-to-date model
of the HV grid capturing the locations of the transformers, their connectivity and the overall topology of the
network including double-circuits. We used the test network provided by Horton et al. (2012) to test our modelling
methodology and to validate the code at the GIC calculation step using a uniform electric field. We then applied the
same methodology to the GB grid and compared the output with a small set of GIC measurements available for the
March 2015 and the September 2017 storm. We find reasonably good agreement between modelled and measured
electric fields and GIC, giving us confidence that our models are providing sensible estimates of GIC at the sites
where we have measurements. However, the GIC measurements are confined to a small region of the grid. As part
of a wider programme, our next step will be to use the differential magnetometer method (DMM) to measure GIC
under individual power lines across the UK over the next two years. We outline the approach that we will take to
reconcile the flow of GIC within our model and the indirect measurements of GIC (as they will not be made at a
transformer ground point). Ultimately, we wish to fully validate the HV grid model of GB (and as a complementary
output the geoelectric field models) from the DMM measurements. This will allow future improvements such as
transformer-level modelling and mitigation strategies to be tested.